The Holby Valve Company offers the first and most-widely specified water
tempering valve in the industry. THE HOLBY TEMPERING VALVE is a temperature
regulating valve, designed to be used as a master, zone, fixture or individual
appliance regulator to control the predetermined temperature of hot water.
Water delivered from hot water generating equipment such as storage tanks, heat
exchangers, submerged coils, or any other source, is frequently too hot or
scalding. This condition can be corrected by the installation of a HOLBY
TEMPERING VALVE. It is a necessary part of any submerged tank less water
heating system.
THE HOLBY TEMPERING VALVE is also used in regulating temperatures for engines,
heating systems, compressors, cooling towers, processing machinery and many
other applications.
DESCRIPTION
THE HOLBY TEMPERING VALVE is rugged, constructed entirely
of bronze and copper and hydrostatically tested to a pressure of 300 pounds. It
has the following features:
- A long mixing chamber with vanes at an angle to the longitudinal axis of
the valve which causes a thorough mixing of the hot and cold water.
- The unusual length of the hydraulic thermostatic element, assures
effective surface contact with the water.
- The thermostatic element is placed in the body of the valve where the hot
and cold water mix. It is immediately sensitive to any change in water
temperature and makes proper corrections by opening or closing the hot and
cold water inlets in the valve.
- The sensitive parts of the thermostatic element are inside a heavy
non-ferrous tube which protects them from any corrosive or scaling action
caused by the continuous flow of water past them.
- The extraordinary length of the thermostatic element provides fifteen to
twenty times the number of corrugations found in the usual short thermostat.
Thus, the total expansion is divided over these numerous corrugations, so that
the flexing of each is reduced to mere thousandths of an inch with resulting
long life of the instrument.
- The action of the thermostatic element moves a piston over the hot and
cold water openings, opening the cold as it reduces the opening of the hot,
thus uniformly blending the hot and cold water, producing an even temperature
of the delivered water without any change in volume. This action eliminates
the building up of temperature in circulating systems at times when little or
no hot water is being used.
INSTALLATION
THE HOLBY TEMPERING VALVE will operate satisfactorily when
installed in any position WITHOUT TRAPPING. It can be installed with a minimum
number of extra fittings, reducing installation costs to a minimum. Its
extraordinary length takes the place of expensive brass pipe. When installing,
our basic piping diagrams should be followed.
The end of the valve, where the adjusting screw is located, should NOT be
placed against, nor in line with any other fixed object for a space of
twenty-four inches. This will allow access to the inner parts of the valve, if
necessary.
Specifications (pdf 228K)
Flow Chart (pdf 205K)